Download on the App Store

Conduit Fill Chart: Complete NEC Wire Fill Table Guide

Every conduit fill calculation starts with the same question: how many wires can you legally pull through this pipe? The answer lives in NEC Chapter 9, specifically Tables 1, 4, and 5. This conduit fill chart puts those NEC wire fill tables in one place so you can size your raceway correctly the first time.

Below you'll find the conduit fill percentage rules, complete conduit fill tables for EMT, IMC, rigid metal (RMC), and PVC conduit, plus a THHN wire fill chart that tells you exactly how many conductors of each gauge fit in each trade size. If you want instant results instead of manual lookups, our conduit fill calculator does the math for you.

NEC Conduit Fill Percentage Rules (Table 1)

Before you touch a conduit fill table, you need to know the fill limits. NEC Chapter 9, Table 1 sets the maximum percentage of a conduit's internal area that conductors can occupy. The percentages change based on the number of conductors.

NEC Chapter 9, Table 1: Conduit fill percentage limits
Number of Conductors Maximum Fill (%) Why This Limit
1 conductor 53% Single conductor centers itself, heat dissipation is even
2 conductors 31% Two conductors can "oval" and jam during pulling
3 or more conductors 40% Standard fill for heat dissipation and pullability
Nipple (24" or less) 60% Short run, minimal heat buildup, no long pulls

The 40% conduit fill rule is the one you'll use most often. Most circuits run a hot, neutral, and equipment grounding conductor at minimum, which puts you at three or more conductors. That 40% limit accounts for heat dissipation (wires packed too tightly overheat) and practical pulling (you need room to snake conductors through without damaging insulation).

EMT Conduit Fill Chart (Table 4)

Electrical metallic tubing (EMT) is the most common raceway on commercial and residential projects. The table below shows the internal area and allowable fill areas for each EMT trade size, pulled directly from NEC Chapter 9, Table 4.

EMT conduit fill areas (NEC Chapter 9, Table 4)
Trade Size Internal Diameter (in) Total Area (sq in) 1 Wire 53% (sq in) 2 Wires 31% (sq in) 3+ Wires 40% (sq in)
1/2"0.6220.30400.16100.09400.1220
3/4"0.8240.53300.28300.16500.2130
1"1.0490.86400.45800.26800.3460
1-1/4"1.3801.49600.79300.46400.5980
1-1/2"1.6102.03601.07900.63100.8140
2"2.0673.35601.77901.04001.3420
2-1/2"2.7315.85803.10501.81602.3430
3"3.3568.84604.68802.74203.5380
3-1/2"3.83411.54506.11903.57904.6180
4"4.33414.75307.81904.57305.9010

To use this table: look up your conduit trade size, then check the column that matches your conductor count. The value in that cell is the maximum total cross-sectional area of all conductors combined. Compare that against the sum of your individual conductor areas from Table 5 (covered below).

Rigid Metal Conduit (RMC) Fill Chart

Rigid metal conduit has thicker walls than EMT, which means a slightly smaller internal diameter for the same trade size. Here are the fill areas for RMC.

Rigid metal conduit (RMC) fill areas (NEC Chapter 9, Table 4)
Trade Size Internal Diameter (in) Total Area (sq in) 1 Wire 53% (sq in) 2 Wires 31% (sq in) 3+ Wires 40% (sq in)
1/2"0.6320.31400.16600.09700.1250
3/4"0.8360.54900.29100.17000.2200
1"1.0630.88700.47000.27500.3550
1-1/4"1.3941.52600.80900.47300.6100
1-1/2"1.6242.07101.09800.64200.8280
2"2.0833.40801.80601.05601.3630
2-1/2"2.4894.86602.57901.50801.9460
3"3.0907.49903.97402.32503.0000
3-1/2"3.57010.01005.30503.10304.0040
4"4.02612.73006.74703.94605.0920
5"5.04720.013010.60706.20408.0050
6"6.06528.895015.31408.957011.5580

IMC Conduit Fill Chart

Intermediate metal conduit (IMC) splits the difference between EMT and rigid. It's lighter than RMC but stronger than EMT. Its internal dimensions fall between the two.

IMC conduit fill areas (NEC Chapter 9, Table 4)
Trade Size Internal Diameter (in) Total Area (sq in) 1 Wire 53% (sq in) 2 Wires 31% (sq in) 3+ Wires 40% (sq in)
1/2"0.6600.34200.18100.10600.1370
3/4"0.8640.58600.31100.18200.2350
1"1.1050.95900.50800.29700.3840
1-1/4"1.4481.64700.87300.51100.6590
1-1/2"1.6832.22501.17900.69000.8900
2"2.1503.63001.92401.12501.4520
2-1/2"2.5575.13502.72201.59202.0540
3"3.1767.92204.19902.45603.1690
3-1/2"3.67110.58405.61003.28104.2340
4"4.16613.63107.22404.22605.4520

PVC Conduit Fill Chart (Schedule 40)

PVC Schedule 40 is common in underground and exposed outdoor installations. Its internal dimensions differ from metal conduit types, so you need the right table.

PVC Schedule 40 conduit fill areas (NEC Chapter 9, Table 4)
Trade Size Internal Diameter (in) Total Area (sq in) 1 Wire 53% (sq in) 2 Wires 31% (sq in) 3+ Wires 40% (sq in)
1/2"0.6020.28500.15100.08800.1140
3/4"0.8040.50800.26900.15700.2030
1"1.0290.83200.44100.25800.3330
1-1/4"1.3601.45300.77000.45000.5810
1-1/2"1.5901.98601.05300.61600.7940
2"2.0473.29101.74401.02001.3160
2-1/2"2.4454.69502.48801.45501.8780
3"3.0427.26803.85202.25302.9070
3-1/2"3.5219.73705.16103.01803.8950
4"3.99812.55406.65403.89205.0220
5"4.97819.461010.31406.03307.7840
6"5.94027.714014.68808.591011.0860

THHN Wire Fill Chart (Annex C)

This is the table most electricians actually want: the maximum number of THHN/THWN-2 conductors allowed in each conduit size at the standard 40% fill. THHN is the most common building wire insulation type, and these counts come from NEC Annex C. No math required.

THHN in EMT

Maximum THHN/THWN-2 conductors in EMT (40% fill, NEC Annex C, Table C.1)
Wire Size 1/2" 3/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 3-1/2" 4"
14 AWG1222356184138241364476608
12 AWG916264561101176266347443
10 AWG51016283863110166217277
8 AWG3691622366396125160
6 AWG147121626466990115
4 AWG1247101628435671
3 AWG114681424364760
2 AWG113571120303950
1 AWG11145814222836
1/0 AWG01134712182430
2/0 AWG01124610152026
3/0 AWG0111359131722
4/0 AWG0111247111418
250 kcmil001113691115
300 kcmil001113571012
350 kcmil00111246811
400 kcmil0001114679
500 kcmil0001113568

THHN in Rigid Metal Conduit (RMC)

Maximum THHN/THWN-2 conductors in RMC (40% fill, NEC Annex C, Table C.8)
Wire Size 1/2" 3/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 3-1/2" 4"
14 AWG1322366285140200308412524
12 AWG1016264562102146224300382
10 AWG6101628396491140188239
8 AWG3691622375381108138
6 AWG24712162638587899
4 AWG1247101623364861
3 AWG114681420304152
2 AWG113571116253443
1 AWG01145812182531
1/0 AWG01134710152126
2/0 AWG0112468131722
3/0 AWG0111357111519
4/0 AWG001124691215
250 kcmil001113571013
300 kcmil00111346811
350 kcmil0001124679
400 kcmil0001113578
500 kcmil0001113457

THHN in PVC Schedule 40

Maximum THHN/THWN-2 conductors in PVC Sch 40 (40% fill, NEC Annex C, Table C.10)
Wire Size 1/2" 3/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 3-1/2" 4"
14 AWG1121345981135192298399514
12 AWG81525435998140217291375
10 AWG5101627376188136182234
8 AWG3591621355078105135
6 AWG14611152536567697
4 AWG1247101622354760
3 AWG113681319304051
2 AWG113571116253342
1 AWG01135811182431
1/0 AWG01134710152026
2/0 AWG0112368131722
3/0 AWG0111357101418
4/0 AWG001124691215
250 kcmil001113571012
300 kcmil00011246810
350 kcmil0001123579
400 kcmil0001113568
500 kcmil0001112457

Conductor Cross-Sectional Areas (Table 5)

When you're working with mixed wire sizes, you can't use the Annex C tables. Instead, you need the cross-sectional area of each individual conductor from NEC Table 5. Add them up, then compare the total against the appropriate column in Table 4. Here are the areas for the most common insulation types.

Conductor cross-sectional areas by insulation type (NEC Chapter 9, Table 5)
Wire Size THHN/THWN-2 (sq in) THWN/THW (sq in) XHHW (sq in)
14 AWG0.00970.01390.0097
12 AWG0.01330.01810.0133
10 AWG0.02110.02430.0211
8 AWG0.03660.04370.0366
6 AWG0.05070.07260.0590
4 AWG0.08240.10870.0814
3 AWG0.09730.12630.0962
2 AWG0.11580.14730.1146
1 AWG0.15620.19010.1534
1/0 AWG0.18550.22230.1825
2/0 AWG0.22230.26240.2190
3/0 AWG0.26790.31170.2642
4/0 AWG0.32370.37180.3197
250 kcmil0.39700.45360.3904
300 kcmil0.46080.52140.4536
350 kcmil0.52420.58880.5166
400 kcmil0.58630.65380.5782
500 kcmil0.70730.78380.6984

Key detail: THHN has a thinner insulation layer than THW, which is why its cross-sectional area is smaller for the same gauge. This means you can fit more THHN conductors in a given conduit than THW. It's one reason THHN is the go-to wire for commercial work.

How to Calculate Conduit Fill (Step by Step)

Here's the process for sizing conduit when you're pulling wire. You can do this by hand with the tables above or let the conduit fill calculator handle it instantly.

Step 1: Count Your Conductors

List every conductor going into the raceway. Include hot conductors, neutrals, equipment grounding conductors, travelers, and any other wires. Remember: the grounding conductor counts toward fill.

Step 2: Determine Your Fill Percentage

Use NEC Table 1 (see above). One conductor = 53%. Two conductors = 31%. Three or more = 40%. Nipples 24" or shorter = 60%.

Step 3: Find Conductor Areas

Look up each conductor's cross-sectional area in NEC Table 5. If all conductors are the same gauge and insulation type, you can skip to the Annex C tables and get a direct wire count. For mixed sizes, add up the individual areas.

Step 4: Select Conduit Size

Find the conduit type you're using in Table 4. Scan down the appropriate fill percentage column until you find a value that equals or exceeds your total conductor area. That's your minimum conduit size.

Worked Examples

Example 1: Simple Circuit in EMT

You need to run three 12 AWG THHN conductors (hot, neutral, ground) through EMT. How small can your conduit be?

Quick check: the THHN in EMT chart shows 9 conductors of 12 AWG fit in 1/2" EMT. You only need 3. Confirmed.

Example 2: Mixed Wire Sizes

You're pulling through rigid conduit: four 10 AWG THHN, two 6 AWG THHN, and one 10 AWG THHN ground. What size RMC do you need?

Example 3: Using the Nipple Exception

You have an 18-inch conduit nipple between two boxes. Can you pull six 10 AWG THHN conductors through 1/2" EMT?

Common Conduit Fill Mistakes

Inspectors catch these on a regular basis. Avoid them.

Understanding NEC Chapter 9

NEC Chapter 9 contains the notes and tables that govern conduit fill calculations. The tables work together as a system. Here's how they connect.

NEC Chapter 9 tables used for conduit fill
Table What It Contains When You Use It
Table 1 Fill percentage limits by conductor count First step: determine your percentage (40%, 31%, 53%, or 60%)
Table 4 Conduit internal dimensions and fill areas Match your total conductor area to the right conduit size
Table 5 Conductor cross-sectional areas by gauge and insulation Calculate total area for mixed-size conductor runs
Table 5A Compact conductor areas When using compact-stranded conductors (less common)
Table 8 Conductor properties (resistance, diameter) Bare wire calculations and voltage drop
Annex C Pre-calculated max conductor counts per conduit Quick lookup when all wires are the same size and type

The critical notes at the beginning of Chapter 9 include the nipple exception (Note 4) and the requirement that all conduit areas are based on the dimensions published in applicable product standards. This is why conduit manufacturers' specifications should match what you see in Table 4.

Using the Conduit Fill Calculator

Looking up tables and doing arithmetic by hand works, but it's slow and error-prone on a busy job site. The conduit fill calculator in the Conduit Bending app handles all of this automatically.

Select your conduit type and trade size, add your conductors (mix sizes freely), and the calculator returns the fill percentage, remaining area, and a pass/fail result against the NEC limit. It uses the same NEC Chapter 9 data shown in the tables above. You can also adjust for nipple runs to apply the 60% limit.

Download Conduit Bending free on the App Store to run conduit fill calculations in the field, along with offset bends, saddles, 90s, and every other conduit math problem you'll run into.

Related Guides

Frequently Asked Questions

What is the 40% conduit fill rule?

The 40% rule comes from NEC Chapter 9, Table 1. When you install three or more conductors in a raceway, the total cross-sectional area of all conductors cannot exceed 40% of the conduit's internal area. This limit ensures conductors can dissipate heat properly and can be pulled without damaging insulation.

How many 12 AWG THHN wires fit in 1/2-inch EMT?

You can fit up to 9 THHN 12 AWG conductors in 1/2-inch EMT at the 40% fill limit. Each 12 AWG THHN conductor has a cross-sectional area of 0.0133 sq in. The 40% fill area of 1/2-inch EMT is 0.1220 sq in. Dividing 0.1220 by 0.0133 gives 9.17, so the maximum is 9 conductors.

What NEC tables do I need for conduit fill calculations?

You need three tables from NEC Chapter 9: Table 1 gives the fill percentages (53% for one wire, 31% for two, 40% for three or more). Table 4 gives the internal dimensions and areas for each conduit type and trade size. Table 5 gives the cross-sectional area of individual conductors by wire gauge and insulation type. Annex C provides pre-calculated lookup tables for common scenarios.

Does the equipment grounding conductor count toward conduit fill?

Yes. Equipment grounding conductors (EGCs) take up physical space inside the conduit, so their cross-sectional area must be included in your fill calculation. They also count toward the total conductor count when determining the fill percentage from Table 1. A typical 20A circuit with a hot, neutral, and ground has three conductors, putting you in the 40% fill category.

What is the conduit fill exception for nipples?

NEC Chapter 9, Note 4 allows conduit nipples (raceway sections 24 inches or shorter) to be filled up to 60% of their total cross-sectional area, regardless of the number of conductors. This is higher than the standard 40% limit because short runs generate less heat and don't require long wire pulls.

How do I calculate conduit fill for mixed wire sizes?

For mixed wire sizes, look up each conductor's cross-sectional area in NEC Table 5 (or Table 5A for compact conductors). Add up the areas of all conductors. Then find the conduit size in Table 4 whose 40% fill area equals or exceeds your total. You can't use the pre-calculated Annex C tables for mixed sizes because those tables assume all conductors are the same gauge and insulation type.

Conduit Bending app icon
Conduit Bending App 16 bend types, bender library, fraction calculator. Free on iOS.
Download on the App Store